Abstract: AS 61869.13:2021 pdf download.lnstrument transformers Part 13: Stand-alone merging unit (SAMU)(IEC 61869-13:2021(ED.1.0) MOD). For a SAMU mounted inside an outdoor cabinet, the maximum temperature for very hot climates shall be increased to...
AS 61869.13:2021 pdf download.lnstrument transformers Part 13: Stand-alone merging unit (SAMU)(IEC 61869-13:2021(ED.1.0) MOD).
For a SAMU mounted inside an outdoor cabinet, the maximum temperature for very hot climates shall be increased to +55 °C. In the
most demanding applications, temperatures up to +70 °C may be specified.
5 Ratings
5.3 Rated insulation levels
5.3.2 Rated primary terminal Insulation level
Subclause 5.3.2 of IEC 61869-1:2007 is not applicable because a SAMU does not have high-voltage primary terminals. Insulation
requirements for analogue inputs connected to instrument transformer secondary circuits are given in 5.3.1301.
5.3.3 Other requirements for primary terminals insulation
Subclause 5.3.3 of IEC 61869-1:2007 is not applicable because a SAMU does not have high-voltage primary terminals.
5.3.4 Between-section insulation requirements
Subclause 5.3.4 of IEC 61869-1:2007 is not applicable because a SAMU does not have high-voltage primary terminals.
Recommended: