Abstract: AS/NZS 2022:2003 pdf download.Anhydrous ammonia-Storage and handling. 2.3.1 General Materials shall be suitable for the conditions of use, and, in particular, arty material in contact with ammonia shall be compatible with ammonia. NOTE Appc...
AS/NZS 2022:2003 pdf download.Anhydrous ammonia-Storage and handling.
2.3.1 General
Materials shall be suitable for the conditions of use, and, in particular, arty material in contact with ammonia shall be
compatible with ammonia.
NOTE Appcndi C gives guidance on the control of risks of stress corrosion cracking of carbon steel in the presence of ammonia.
2.3.2 Minimum design temperature
Materials shall he selected and equipment shall bc designed for a minimum temperature appropriate for the duty and in accordance
with the applicable design Standard. The atmospheric boiling point of ammonia is —33.3?C and this temperature would usually
represent the minimum operating temperature for tanks and other equipment containing liquid anhdrous ammonia capable of being
depressuriicd to atmospheric conditions. Lower equilibrium temperatures are possible at ammonia partial pressures less than
atmospheric. (See Appendix A.)
2.4 ILECTRICAL EQIIPMFNT AND WIRING.
Flcctrical equipment and wiring for use in anhydrotis ammonia installations shall be installed and maintained in accordance with
AS/NZS 3000.