AS 2005.10:1988 pdf download

From:Internet 2022-10-01 15:16

Abstract: AS 2005.10:1988 pdf download.Low VOLTAGE FUSES—FUSESWITH ENCLOSED FUSE-LINKS Part 10—GENERAL REQUIREMENTS. 5.3.2 Rated current of the fuse-holder. The rated current of the fuse-holdcr. cxprcssed in amperes. should be selected from the s...

AS 2005.10:1988 pdf download.Low VOLTAGE FUSES—FUSESWITH ENCLOSED FUSE-LINKS Part 10—GENERAL REQUIREMENTS.

5.3.2 Rated current of the fuse-holder. The rated current of the fuse-holdcr. cxprcssed in amperes. should be selected from the

series of rated currents of fuse-links (if not otherwise specified in other Standards of the AS 2005 series). For gG’ and aM fuses the rated current of the fuse-holder represents the highest rated current of the fuse-link with which it is intended to be used.

5.4 RATED FREQUENCY. See Clauses 6.1 and

6.2. The absence of any marking regarding rated frequency shall imply that the fuse meets the conditious laid down in this Standard for frequencies between 45 Hz and 62 Hz only.

5.5 RAVED POWER DISSIPAllON OF A FUSE- LINK AND RATED POWER ACCEPTANCE OF A FUSE-hOLDER.

The ruled power dissipation of a fuse-link is stated by the manufacturer if not otherwise specified in other Standards of the AS 2005 series. That value shall not be exceeded under specified test conditions.

The rated power acceptance of a fuse-holder is stated by the manufacturer if not otherwise specified in the other Standards of the AS 2005 series. It is intended to be the maximum poer dissipation that the fuse-holder can tolerate under specified test

conditions without exceeding the specified temperature rise.


Recommended:

Download Address
Related Standards