Abstract: IEC 60694:2002 pdf free download.Common specifications for high-voltage switchgear and controlgear standards. 2.2 Special service conditions When high-voltage switchgear and controlgear may be used under conditions different from the normal...
IEC 60694:2002 pdf free download.Common specifications for high-voltage switchgear and controlgear standards.
2.2 Special service conditions
When high-voltage switchgear and controlgear may be used under conditions different from the normal service conditions given in 2.1, the user’s requirements should refer to standardized steps as follows.
2.2.1 Altitude
For installation at an altitude higher than 1 000 m, the insulation level of external insulation under the standardized reference
atmospheric conditions shall be determined by multiplying the insulation withstand voltages required at the service location by a
factor Ka in accordance with figure 1.
NOTE 1 Fot ntrn ènsulation, the d.lectflc characterishcs are d•ntical at any altitude and no special precautions need to be taken. For external and lnteinal nsulatlon. see IEC 80071-2.
NOTE 2 For Iow.voltage auxiliary arbd control equipment, no special precautions need to be taken 1 the al lowr than 2 000 m For
higher altitude, see IEC 60664-1.